Current
Supply
-
5
Amps (maximum) through current transformer
or direct from the circuit as the case may
be
-
For
three phase system It is the current from
the B Phase
-
For
one phase system it is the current in line.
Trip
Time
Trip
Time is adjustable from 2 to 10 seconds with the
help of a knob provided on top of the unit with
call berated dial.
Reverse
Power Sensitivity
It
is approximately 0.25 A 0.25 Amps of C.T.
secondary in the reverse direction. Getter or
different sensitivity can be given on specific
demand.
Power
Factor
For three phase system the relay can operate on
both leading and logging power without any difference.
But for one phase system the relay is suitable
one for lagging power factor and trips on leading
power factor.
Output
Two sets of change-over contacts (Potential Free)
and suitable for & Amps resistive load at
240VAC/415VAC or 24VDC.
Reset
Both
Auto and Manual reset models are available. Operation
for both the models is explained in description
given above.
Burden
Voltage
Supply : 10VA (maximum), Current Supply : 2VA
(Maximum)
Dimensions
Base-----70
x 120mm, Height----125mm
|
Mounting
Details
|
|
Recommended mounting screw size 5mm
(3/16)
|
|
External Connection
|
|

|
| |
|