Current
Setting Range
1 to 5 amps AC (for
higher current suitable CT's should be used)
Max capacity of
the current sensor is 10 amps.
Setting
Accuracy
±
2% of the time and current setting
Operating Voltage
12
or 24 VDC (±25%)
110 or 240 or 415
VAC (±25%)
or
any other voltage as per requirement.
Relay
Contact Rating
6 Amps resistive
load or 2 Amps inductive load at 230 VAC/440 VAC
or 24 VDC
Insulation
The unit will withstand
2.5 KV 50 Hz for one minute between all external
A.C. supply termina's and relay contacts connected
together and body.
Dimensions
Height 105 mm, Width 51mm, Length 102mm
Burden
Voltage Supply :
5 VA (Max.)
Current Supply : 1 VA (Max.)
|
Mounting
Details |
|
Recommended mounting screw size 5mm
(3/16)
|
|
External Connection |
|

This
device can be used for both 1Ø and 3Ø
earth faults. For 3Ø earth fault, single
CT can be used by passing all the three
phase and neutral wires through the
CT and in case of bus bars, matching
CT's are put on each bus bar and then
paralleled with each other. |
|